FurnaceBlinkCode // GOODMAN • AMANA • DAIKIN
OEM PCBBF112S / PCBBF134S / B18099-13 / 50A55-843 • Single Red LED & 7-Segment Matrix

Goodman, Amana & Daikin Furnace Blink Codes Decoder (1–7 Red Flashes)

⚡ Instant OEM Answer (Goodman / Amana / Daikin Red LED System): On Goodman, Amana, and Daikin furnaces, 4 Flashes indicates an open Primary High Limit Switch (20162904, caused by a dirty filter in 65% of calls); 3 Flashes indicates an open Inducer Pressure Switch (0130F00505, -0.75" WC); 1 Flash or 7 Flashes indicates Ignition Lockout / Low Flame Sense (0130F00010 sensor below 0.8 µA DC or 0130F00008S igniter open); and 6 Flashes indicates a tripped manual Flame Rollout Switch.
Single-LED & ComfortBridge 7-Segment Reference

Complete Goodman, Amana & Daikin LED & 7-Segment Fault Matrix

Covers Goodman GMP, GMT, GMS8, GMES80, GMSS96, GMEC96, GMVC96, Amana AMSS96, AMEC96, AMVC96, and Daikin DM80/DM96 furnaces using single-LED (PCBBF112S, PCBBF134S, B18099-13, 50A55-843) and 3-digit 7-segment (PCBBF136S, PCBBF140, ComfortBridge) boards.

Single Red LED 7-Segment Code Goodman / Amana OEM Meaning OEM Replacement SKU & Triage Fix
Steady Red ON IdL / 1Ht / 2Ht Normal Standby or Active Heating Healthy 24VAC & intact 3A purple fuse. Check thermostat W1 call.
1 Flash EE0 1-Hour System Ignition Lockout (3 Retries) Polish 0130F00010 Flame Rod (2.0–6.0 µA DC) or test 0130F00008S Igniter (40–75 Ω Carbide / 11–20 Ω Nitride).
2 Flashes EE1 Pressure Switch Stuck Closed (Inducer Off) Drain droplet from silicone hose or swap welded 0130F00505 Pressure Switch ($38).
3 Flashes EE2 / EEA Pressure Switch Stuck Open (Inducer Running) Ream metal inducer hose barb with paperclip, flush condensate trap, clear outdoor PVC pipes.
4 Flashes EE3 / EEL Primary or Auxiliary High Limit Switch Open Replace dirty air filter immediately; test 20162904 Primary Limit & blower run capacitor µF.
5 Flashes EE4 False Flame Detected With Gas Valve Closed Inspect White-Rodgers 36G22 / 36J22 gas valve for shutoff seep or moisture on board flame pin.
6 Flashes EE5 Manual-Reset Flame Rollout Switch Open CRITICAL: Inspect tubular heat exchanger & flue before pressing 10123529 rollout reset button.
7 Flashes EE6 Weak Flame Microamp Sense (Or Lockout on 50A55) Clean 0130F00010 Flame Sensor rod before marginal 0.9–1.3 µA drops into midnight lockout.
Rapid Continuous EEJ / E11 115V Line Polarity Reversed or Floating Ground Add $14 Neutral-Ground Bonding Plug on portable inverter generators; verify L1-to-Ground 120VAC.
💡 Pro Goodman Attic Triage Tip (Hidden Blower Housing Auxiliary Limits): If your horizontal attic Goodman or Amana furnace continues blinking 4 Flashes (`EE3`) even after the unit is cold and the main rectangular `20162904` primary limit reads `0.0 Ω`, reach into the lower blower compartment and feel the two small disc switches screwed to the curved steel blower scroll housing. Many horizontal Goodman units use manual-reset button auxiliary limits (`B13701-54`) that stay open indefinitely after a power blink until you press the tiny red pin between the two wire spades!