Lennox Furnace Dual Red & Green LED Decoder: SureLight DS1 + DS2 Matrix

⚡ Instant OEM Answer (Lennox Dual Red DS1 + Green DS2 LEDs): Lennox SureLight boards pair a Red (DS1) and Green (DS2) LED: Simultaneous Slow Flash means normal standby; Alternating Slow Flash means 60-minute Watchguard Ignition Lockout (clean 52W29 flame sensor below 1.5 µA DC or check 11–19 Ω Nitride igniter); Red OFF + Green Slow Flash means Pressure Switch open; and Red Slow Flash + Green OFF means Primary High Limit open.
Dual-LED DS1 & DS2 Reference

Complete Lennox SureLight DS1 (Red) + DS2 (Green) Combination Table

Applies to Lennox G40UH, G43UF, G50UH, G51MP, G60UH, G61MPV, ML180, ML193, EL195, Ducane 80G1/92G1, and Aire-Flo furnaces equipped with dual-LED SureLight integrated controls (56L84, 63K89, 83M00, 97L48, 103085-03).

Red LED (DS1) Green LED (DS2) Lennox OEM Fault Meaning Replacement Part SKU & Triage Fix
Slow Flash (Together) Slow Flash (Together) Normal Standby — Power OK Zero faults. Simultaneous Fast Flash = Active Heating Demand.
Alternating Slow Alternating Slow 60-Min Watchguard Ignition Lockout Polish 52W29 / 69W43 Flame Sensor ($0) or swap 768A-845 / 41K56 Igniter ($45).
OFF Slow Flash Pressure Switch Open / Blocked Flue Flush Lennox condensate trap, clear PVC vent snow, or test 80W52 / 11U64 Switch.
OFF Fast Flash Pressure Switch Closed Before Inducer Drain condensate water droplet from silicone hose or replace welded pressure switch.
Slow Flash OFF Primary High Limit Switch Open Replace dirty air filter immediately; check closed vents & blower run capacitor µF.
Fast Flash OFF Manual Flame Rollout Switch Open CRITICAL: Inspect heat exchanger & burner vestibule before pressing rollout reset button.
Alternating Fast Alternating Fast Improper 120V Line Polarity / Ground Verify 120 VAC L1-to-Ground and < 2.0 VAC Neutral-to-Ground (or add generator bonding plug).
Steady ON Steady ON (Or Both OFF) Internal Control Fault or Open 3A Fuse Check 3A purple blade fuse & 24VAC transformer; if solid ON with 24VAC present, replace board.